Condition testing of circuit breaker’s arcing contacts

BY BUDO MILOVIC, DV-Power

The preventive maintenance on a high-voltage (HV) breaker consists of several routine tests. The timing and motion tests are methods used to assess the breaker’s mechanical condition. When the timing and motion results indicate an abnormality, the dynamic resistance measurement (DRM) test can be an effective way to further diagnose the internal condition of the breaker contacts. As an example, a high-voltage puffer-type sulfur hexaflouride (SF6) gas circuit breaker is based on the switching of two parallel contact sets. First, the low-resistance silver-plated contacts, or the main contacts, are designed specifically to carry the load current without any excessive temperature rise.

The second, tungsten-copper arcing contacts operate at the breaker opening following the main contact part. The electrical arc starts after the separation of the arcing contacts. The tungsten-copper material is designed to carry the arc until it is cleared at the next zero-crossing.

Live Online & In-person Group Training

Advantages To Instructor-Led Training – Instructor-Led Course, Customized Training, Multiple Locations, Economical, CEU Credits, Course Discounts.

Request For Quotation

Whether you would prefer Live Online or In-Person instruction, our electrical training courses can be tailored to meet your company's specific requirements and delivered to your employees in one location or at various locations.