Designing Refiner Motors to Withstand Switching Voltage Transients
By R.H. Rehder, W.J. Jackson,and B.J. Moore
During the past 25 years, the capacity of typical single-disc thermal
mechancial pulp refiner motors has increased by a factor of three (see Figure
1). With pulp output concentrated in fewer machines, the reliability associated
with larger motors becomes increasingly significant.
Stator winding insulation systems are a critical component affecting over-all
motor reliability. Paralleling the development of TMP pulping technology since
the 1970s, has been the introduction and continuous improvement of high-voltage
(up to 15 kV) resin vacuum pressure-impregnated (VPI) stator insulation systems.
The use of improved materials along with a more comprehensive understanding of
the physics related to the aging and failure mechanisms of dielectric systems
have resulted in stator insulation systems that achieve the high reliability
expected of larger refiner motors.
In the past, insulation systems for refiner motors have been primarily
designed and tested based on line-frequency voltages. Some equipment, such as
switchgear and transformers, was designed for occasional lightning and switching
surges, and impulse testing used to verify an impulse withstand level or basic
impulse level (BIL) for the equipment. In the past 20 years, triggered by the
introduction of vacuum circuit breakers, rotating machine designs have taken
into account switching surges as a design parameter.
In the 1950s, turn-to-turn insulation was based on line-frequency voltages of
the order of 100 or 200 volts RMS per turn. Then it was realized that transient
and surge voltages caused severe turn-to-turn voltage stress, and the first
issue of IEEE 522 [1] recommended a two per unit voltage capability with a 0.2
microsecond rise time based on line-to-ground peak voltage. Most manufacturers
selected their turn-to-turn insulation to meet this two per unit factor.
Investigations by utilities [2,3,4] in the mid-1980s established that operation
of both vacuum and air-magnetic circuit breakers introduced multiple voltage
surges or spikes that had a peak magnitude at the motor terminal box as high as
4.6 per unit (line-to-ground peak voltage), with a rise time to peak as low as
0.1 microseconds.
Subsequently, IEEE Guide 522 was revised to include a 3.5 per unit test value
instead of a two per unit level for those applications that could be termed as
high surge applications, Fig. 2. NEMA standard MG 1-1993, Part 20.87.5 [5]
recognizes the higher impulse withstand envelope of IEEE 522, but the motor
buyer must specify the increased capability at the time of purchase. These
switching transients are not continuous and usually occur on circuit breaker
opening and closing operations. There are still some motor manufacturers that
have not changed their design practices to use the 3.5 per unit value in place
of the previous two per unit recommendation, and therefore their turn-to-turn
insulation could be at risk under some breaker operating conditions.
Some vacuum breaker manufacturers realized early in their development of the
vacuum interruptors that re-strikes could create voltage spikes and they
supplied, with their switchgear assemblies, suitable surge suppressors or
arrestors to limit the peak transient voltages [6]. Every feeder breaker
designated for motor switching was equipped with these suppressors. Some
manufacturers of vacuum interrupters have introduced different metals into their
contacts to reduce restrike transients, but this can have an adverse effect on
the interrupting capability of the contact design. Careful design of the breaker
mechanism with sufficient wipe and contact separation speed can also improve the
transient switching performance of vacuum breakers. There are a number of
technical papers describing the re-strike phenomenon [7,8,9].
Transient Effects
The transient voltages have a rise time of 0.1 to 0.2 microseconds to crest
value. This fast rate of rise is equivalent to a frequency between 1.25 and 2.5
MHz. The transient is a traveling wave phenomenon that impinges on the motor
stator winding, stressing the turn-to-turn insulation of the first turn. As the
transient travels along the turns of the first coil, it loses some of its energy
due to capacitive leakage to the grounded stator and capacitive coupling between
turns. At the end of the first coil there is a change in the surge impedance due
to the shape of the series connection to the second coil. This results in a
minor voltage reflection, increasing the voltage stress on the last turn of this
first coil.
As the transient passes to each of the remaining coils, the crest voltage and
the rate of rise of that crest decrease. Therefore, transient-related insulation
failures usually occur as a turn-to-turn fault on the first or terminal coils in
a machine. Transients with slower rise times (>5 m-msec, corresponding to a
frequency of 50 kHz) distribute themselves over the winding more gradually,
resulting in lower turn-to-turn voltage stress. The voltage stress distribution
in the machine from terminal to neutral connection will vary from machine to
machine depending on the surge impedance of the winding. Using the IEEE 522
surge factor of 3.5 per unit, the required turn insulation capability can be
selected on the basis of the following formula:
Vt 3.5(Vp-p/sr3) (sr2)/T
where:
Vt = turn-to-turn voltage capability in crest volts;
Vp-p = phase-to-phase RMS voltage at system frequency;
sr =square root
T = number of turns per coil.
As an example, the minimum required turn-to-turn voltage capability for a
motor on a 13.8-kV system with a five-turn coil would be 7.9 kV crest per turn.
The turn-to-turn insulation thickness will probably be in the range of 1.0-mm
(40-mil), so the average voltage stress is approximately 7.9 kV peak volts per
mm (200 peak volts per mil). Ground wall insulation, conductor to ground average
stress, is in the range of 2.8 kV peak volts per mm (70 peak volts per mil).
In general, the turn-to-turn insulation is stressed higher than the ground
wall insulation, and therefore the turn-to-turn insulation should receive
special attention both from a design and a manufacturing standpoint.
Void-Free System
The distribution of electric stress with more than one dielectric in series
is inversely proportional to their respective dielectric constants.
In a system with two dielectrics, Fig. 3, the voltage distribution follows
the relationship:
V1 = [K2S1 / (S1K2+S2K1)] V
where:
V1 = voltage across insulation with dielectric constant K1;
V2 = voltage across insulation with dielectric constant K2;
V = total voltage across system;
S1 = thickness of insulation with dielectric constant K1;
S2 = thickness of insulation with dielectric constant K2.
For example, assume a turn-to-turn insulation that has a thickness of 1.0 mm
(40 mils), and a 0.025-mm- (1 mil-) thick air gap or void occurs in the
insulation. Based on an insulation with a dielectric constant of 3.5 and with
the dielectric constant for air as 1, the voltage across the air gap will be 8
per cent of the total voltage applied. With a 7.9-kV voltage stress, the air gap
or void will have 633 peak volts or 447 volts RMS. This stress in the air is too
high and the air breaks down with a partial discharge. The partial discharge
activity will cause deterioration of the insulation with time, and ultimately
there will be a failure of the insulation system.
Electrically, the insulation system can be represented by parallel or series
connections of a resistor and a capacitor. Figure 5 is a parallel
representation, one branch having a void in the solid insulation; it also shows
a vector diagram, where the angle d is known as the loss angle. Poor insulation
systems will have a large loss angle because the IR vector (leakage current)
will be large. The tangent of this angle is referred to as the dissipation
factor (DF) or tan delta, which is often considered as a measure of the quality
of the insulation system. Poorly compacted or void-filled insulations will have
a high DF. For rotating machines with VPI insulation systems, the DF for a full
phase winding at rated voltage should be less than 4 per cent, or the tangent of
the loss angle must be less than 0.04.
Paschen's Curve
The breakdown characteristics of air can be approximated by a modified
Paschen's curve, Fig. 5. If the voltage stress across the air gap or void in the
system is greater than the breakdown strength of the air, as was the case in our
example, then partial discharges will occur and the system will deteriorate with
time. Note that there is a minimum voltage at which breakdown can occur. Gaps
smaller than 6 mm (0.24 mils) will require higher voltages to break them down.
It also indicates that as long as the voltages are below 280 volts RMS, partial
discharge would not occur and very small air gaps would not be critical. The
curves are based on standard atmospheric pressure and using electrodes with a
diameter of 12.7 mm (1/2 inch). A decrease in electrode diameter will lower the
breakdown value. High frequencies in the megahertz range will also lower the
breakdown voltage.
Areas of Concern
The cross section of a large high-voltage coil is shown in Fig. 6. In VPI
systems, there have been some manufacturing problems in ensuring that the
impregnating resin penetrates between turns to eliminate air voids in this area.
As well, there is concern in filling the triangular space between turns at the
location marked "A" in Fig. 6 [10].
Some manufacturers use a resin with a very low viscosity to ensure that there
is complete penetration. The disadvantage to this low-viscosity approach is the
tendency for the resin to flow out of larger void areas during the time between
the impregnation of the resin and the baking process to cure the resin. One of
the ways to overcome these difficulties is to use resin rich mica tapes for the
turn insulation. The tapes are applied to the strand bundle as the coil bobbin
or loop is formed. After spreading, the slot sections of the coil are placed in
a press and heat and pressure are applied. The heat and pressure causes the
resin, which is now already in the turn-to-turn location, to flow and displace
any air during the curing process.
As the coil section is held within irons during the pressing procedure, the
turn package is rectangular, with a flat surface along the sides of the coil and
the air spaces at "A" have been eliminated. The ground wall insulation
is applied over these pressed turns and the conventional VPI process is followed
for the remainder of the insulation system. The major benefit of the pressed
turn is minimizing the chance of air voids in a critical area of the system. On
high-voltage coils the VPI resin must work its way from outside the coil,
through the thick ground wall insulation, and with the pressed turn system the
VPI resin does not need to penetrate beyond the turns to the strands.
The electrical stress is highest at the surface of the conductor. Dielectric
field plots have indicated that the electrical stress at the corners of the
coil, next to the copper, can be double the stress along the side of the coils.
Figure 8 is a diagram showing the equipotential lines at the corner of a stator
coil. Note that the lines are closest together next to the copper. Therefore,
voids or deficiencies in the insulation next to the strands and turns are
critical, and damaging partial discharges will occur first in these areas. For
this reason, the use of corona-resistant enamels as a strand insulation can
delay the propagation of a fatal carbon track through the insulation and
increase the life and reliability of the system.
The use of non-film-backed tapes, the elimination of corona-sensitive
materials and the use of fillers to give corona-resistant characteristics to
tapes and resins also improves life. Figure 8 is a curve of voltage endurance
showing the extended life that can be achieved with the use of corona-resistant
materials.
Using Capacitors
Provided the turn-to-turn insulation has been designed to meet the 3.5 per
unit surge factor, capacitors, arrestors and resistors would not be required to
protect the stator winding turn insulation. However, capacitors and arrestors
have been applied for many years and they will protect against power system
surges due to system switching operations and lightning strikes on the supply
system. They do slope the wave front of surges and minimize the magnitude. This
distributes the stress in the winding and will reduce transient partial
discharge activity. They are good insurance.
The addition of series resistors with the capacitors to critically damp the
motor, cable and supply system so that multiple restrikes on vacuum breakers do
not occur, has some disadvantages. The resistors reduce the amount of wave
sloping produced by the surge capacitors. The selection of the resistors is
dependent on the surge impedance of each specific cable run from the switchgear
to the motor terminals, as well as the impedance of the source bus and its
connected loads, such as other motors. If additional motors are added to the
bus, or conversely a motor is removed, then the resistors lose some of their
effectiveness and should be replaced. Non-inductive resistors are complex to
design, particularly considering that they must be capable of withstanding any
initial single surge voltage, terminal to terminal. Non-inductive resistors are
usually counter wound so that electrical clearances are limited.
Conclusions
New motors are available that are capable of withstanding potential
re-strikes produced by vacuum interrupters. Older motors, designed to the two
per unit surge value, should have arrestors and capacitors, and it may be
practical to add partial discharge monitors to the machine so that there would
be an advanced indication of deterioration due to transient partial discharges
caused by breaker operations [11].Adding resistors in series with the surge
capacitors is adding complexity to the installation and additional insulation
paths to ground.
These factors could be adversely affecting reliability relative to a motor
designed initially to meet the 3.5 per unit turn-to-turn levels described in
IEEE 522 along with the use of advanced corona-resistant materials.
Purchasers of large refiner motors should specify a stator insulation system
that is capable of meeting the higher IEEE surge withstand envelope.
Furthermore, all stator coils should be impulse tested individually after
installation in the stator but prior to connection.
References
1 IEEE Std 522-1992 IEEE Guide for Testing Turn-to-Turn
Insulation on Form-Wound Stator Coils for Alternating-Current Rotating Electric
Machines. (1992). 2. GUPTA, BA., LLOYD, BA., STONE, G. C., CAMPBELL, SR.,
SHARMA, DR., NILSSON, N.E. Insulation Capability of Large AC Motors. Part 1 Ñ
Surge Monitoring. Trans., IEEE on Energy Conversion, EC-Number 4,658-665,
December (1987).
3. GUPTA, BA., LLOYD, BA., STONE, CC., SHARMA,D.K., FITZGERALD, J.P.
Insulation Capability of Large AC Motors. Part 2 Ñ Impulse Strength. Trans.,
IEEE on Energy Conversion, EC-2 Number 4,666-673, December (1987).
4. GUPTA, BA., LLOYD, B.A., STONE, G.C., SHARMA, D.K., NILSSON, N.E.
Insulation Capability of Large AC Motors. Part 3 Ñ Insulation Coordination.
Trans., IEEE on Energy Conversion, EC-2 Number 4, 674-679, December (1987).
5. National Electrical Manufacturers Association (NEMA). Standards
Publication No. MG 1-1993, Motors and Generators. NEMA (1993).
6. KURTZ, D.R., PANEK,J., TITUS, C.H., WALSH, G.W. Transient Voltage
Performance of Vacuum Metalclad Switchgear. Proc., lAS Annual Meeting, IEEE
Industrial Applications Society, Chicago, IL, 872-877,October (1976).
7. EICHENBERG;J.P., HENNENFENT, H., LILJESTRAND, L. Multiple
Re-Strikes Phenomenon when Using Vacuum Circuit Breakers to Start Refiner
Motors. Proc., IEEE 1998 Annual Pulp & Paper Conference, Portland, ME,
266-273,June (1998).
8. FARAG, S.F., BARTHELD, R.G. Guidelines for the Application of
Vacuum Contactors. Trans., IEEE on Industry Applications. Vol. 1A-22,
No.1,102-108, January/ February (1986).
9. GREENWOOD, A.N., KURTZ, D.R., SOFIANEK, J.C. A Guide to the
Application of Vacuum Circuit Breakers-Trans., IEEE. Vol PAS-90: 1589-1597
July/August (1971).
10. WALKER, P., CHAMPION, J.N. Experience with Turn Insulation Failures in Large
13.2 kV Synchronous Motors. Trans., IEEE on Energy Conversion, EC.6 Number 4,
670-678, December (1991).
11. NASSAR, O.M. The Use of Partial Discharge and Impulse Voltage Testing in the
Evaluation of Interturn Insulation Failure of Large Motors. Trans., IEEE on
Energy Conversion, EC-2 Number 4,615-621, December (1987)
W.J. Jackson and B.J. Moore are with GE Canada. R.H. Rehder is a consultant.
This article is based on a paper presented at the 86th Annual Meeting of the
Technical Section, CPPA, in Montreal, QC. ET