ASD Motor Protection

The Use Of ASDs and VFDs Can Damage Motors But There Are Ways To Protect Them


By Mahesh Swamy and John A. Houdek
The use of Adjustable Speed Drives (ASD), also known as Variable Frequency Drives (VFD), has gained tremendous popularity in recent times because of their power savings and speed control features. The voltage waveform being applied across the windings of an induction motor being fed from an ASD is Pulse Width Modulated (PWM). In general, the output is modulated at a carrier frequency ranging from 1.0 kHz. to 19.0 kHz. When the distance between the motor and the ASD is long and there exists a mismatch in the cable and motor surge impedances, there is voltage amplification at the motor terminals. This is attributed to a phenomenon known as Voltage Reflection. The overvoltage at the motor terminals, which depends on the distance between the motor and the ASD as well as on the impedance mismatch between the cable and the motor surge impedances, can reach as high as 1.9 times the DC bus voltage of the ASD. The over-voltage can cause premature insulation failure in the motor.

The phenomenon of reflection of electromagnetic (em) waves on an electrical conductor is very similar to a wave in water. At a given point, the magnitude of the water wave varies with time and its phase is retarded. As one moves away from the origin of the wave, the amplitude diminishes and eventually subsides. However, if there is a barrier to the wave movement, there is reflection. Consequently, the amplitude of oscillation at a given point is the sum of the incident and the reflected wave at that point. Similar results are observed when an em wave travels on a transmission line. If a load on a transmission line is physically at infinite distance from the source, there exists no reflection similar to a water wave originating in a pond with boundary at infinity. One can electrically create an infinite transmission line (a line having no reflection) if the surge impedance at the terminating end matches the cable surge impedance. However, in most cases the motor and cable surge impedances are mismatched which causes voltage reflections; voltage reflection further causes voltage amplification at the motor terminals since the motor and the ASD are usually physically separated by long lead lengths. Long Transmission Line Theory as Applied To Motor-ASD Case
Let the voltage at any given point which is x meters away from the load end, be denoted by Vx. This voltage is the sum of incident and reflected waves at that point. Let the incident wave be denoted as v+ and the reflected wave be denoted as v-. Vx is given by:

Vx = v+ + v- (1)

Referring to Figure 1, it is evident the incident wave, v+, is equal to the sum of the receiving end voltage and the drop across the surge impedance of the cable. Similarly, the reflected wave, v-, is equal to the difference between the receiving end voltage and the drop across the surge impedance. From these observations, one can rewrite the voltage at any given point on the transmission line as follows:

Vx is voltage at a point x units away from the receiving end;

VR is voltage at receiving end;

IR is current at receiving end;

ZC is characteristic impedance of line; = L/C;

L is phase inductance per unit length;

C is line-ground capacitance per unit length;

y = + j;

is attenuation constant;

is phase constant;

The exponential terms are used in equation (2) to help explain the variations of the voltage waveform as a function of the distance along the line. The first term in equation (2) denotes the Incident wave while the latter term in equation (2) denotes the Reflected wave. Based on equation (2), the following points are worth noting:

(a) x is zero at the receiving end and increases as one moves away from the receiving end towards the point of interest on the transmission line. On moving away from the receiving end (for increasing values of x), the incident wave increases in magnitude and advances in phase;

(b) On moving away from the receiving end (for increasing values of x), the reflected wave diminishes in magnitude and retards in phase;

(c) If the terminating point is at infinite distance from the point of interest (i.e., x is at infinity), then there exists no reflected wave;

(d) If the terminating impedance is equal to the characteristic impedance, i.e., ZR = ZC, there exists no reflected wave. A line terminated in its characteristic impedance is known as a flat line or an infinite line.

Bundled conductor lines have lower values of ZC as they have lower L and higher C than lines with single conductors per phase;

(e) From equation (2), it is interesting to note that under no load conditions, IR = 0. This results in the incident wave to be equal and in phase with the reflected wave at the point of termination, i.e., at x = 0. Hence, the actual voltage at the point of termination which is given by equation (1), equals 2 times the incident voltage wave. This shows the voltage doubling effect under open or no load conditions;

Coefficient of Reflection
As explained earlier, any em wave traveling on an electrical conductor exhibits the phenomenon of reflection, exception being an infinite transmission line or a line terminated in its characteristic impedance. Referring to Figure 1, the value of the terminating impedance, ZR, is given by the ratio of the voltage and current at the point of termination. The voltage and current components are made up of the incident and reflected waves. Mathematically, this can be represented as:

ZR is the terminating impedance;

vR+ is the incident voltage wave at termination;

vR- is the reflected voltage wave at termination;

iR+ is the incident current wave at termination;

iR- is the reflected current wave at termination;

Further, the incident and reflected current components can be expressed as:

iR+ = vR+/ ZC (4)

iR- = vR-/ ZC (5)

Substituting for iR+ and iR- in equation for ZR:

The ratio of the reflected wave to the incident wave is known as the coefficient of reflection and is denoted as PR at receiving end. For voltage, the coefficient is:

The reflection phenomenon exists at the sending end as well. The coefficient of reflection at the sending end is denoted by PS. For voltage, the coefficient is:

From equations (7) and (8), a few interesting remarks can be made:

(a) If at point of termination there is a short-circuit, then ZR = 0; and PR = -1; vR-= - vR+ and so the sum of reflected and incident voltages at the point of termination is Zero, i.e., (vR- + vR+ = 0);

(b) If the point of termination is an open circuit, then ZR = ; PR = 1; and so the sum of reflected and incident voltages at point of termination is 2vR+;

(c) If at the point of termination, ZR = ZC; then there exists no reflection since PR = 0;

(d) Mismatched impedance causes overvoltage when ZR >> ZC and PR approaches a value of Unity; If ZR<< ZC, then PR is negative, and reflection exists but it does not result in voltage amplification at termination;

(e) As mentioned earlier, coefficient of reflection for Source (PS) exists as well; typically, source impedance ZS , is Zero and hence, PS is approximately -1; Note that under ideal conditions, the rms value of sending end voltage does not change from its nominal value;

Applying the above theories to the case of a motor being fed via an ASD, one can come to a few interesting conclusions. The mismatch between cable and motor surge impedance is the highest for small motors; Also, in all cases, the coefficient of reflection is positive, which means that there always exists amplification of the voltage at the motor terminals. Typical motor and cable surge impedances for popular sizes of motors is given below [2]:

HP ZR ZC PR

25 1500 80 0.9

50 750 70 0.83

100 375 50 0.76

200 188 40 0.65

400 94 30 0.52

Smaller hp motors have larger inductance and less amount of slot insulation which results in a higher surge impedance compared to larger hp motors.

Critical Cable Length
The phenomenon of reflection occurs irrespective of the distance between the motor and the ASD as evidenced from the discussions in the preceding paragraphs. The magnitude of the voltage at a given point on the transmission line is a function of the distance x from the terminating point as shown by equation (2). The worst case of reflection at the terminating point occurs under open circuit conditions. In order to estimate the critical length at which the magnitude of the sum of the incident and reflected wave is higher than the peak value of the incident wave, one has to know the speed of propagation of em waves on the transmission line.

If the speed of propagation of the em wave is assumed to be v and the rise time of the PWM wavefront (defined as the time taken for the output to go from 10 per cent to 90 per cent of its peak value) is tr, then the distance traveled by the wavefront during its rise time is simply v x tr. If the terminating point is at a position where the incident wave has just reached 50 percent of its full value and if total reflection is assumed, i.e., PR = 1.0, then the sum of the incident and reflected waves will yield 100% of the peak value of the incident wave. Any distance greater than this critical length would allow the incident wave to build up to more than 50 per cent of its peak value and if total reflection is considered, the effective wavefront at the terminating point will be greater than 1.0 p.u. Thus the critical cable length is given by:

The speed of propagation of a wavefront over the conductor depends on the inductance and capacitances per unit length of the conductor. Mathematically, it is given by:

Typical values for the speed of propagation, v, range from 100 to 150 m/ sec. The rise time of typical IGBTs used in ASDs range from 0.4 to 0.6 sec. Using equation (10), the critical length is calculated to vary from 20 to 45 meters.

Mitigation Techniques
As shown in the preceding paragraphs, in most long lead length cases involving induction motors fed from ASDs, there exists voltage amplification. This overvoltage at the motor terminals can deteriorate the insulation system of the motor thereby causing premature motor failures. Four different techniques are discussed in this section which help alleviate the overvoltage problem encountered by motors fed from ASDs at long distances. These four techniques are: the use of 3-phase load reactors; the use of RC snubbers at the motor terminals; applying low pass filter section to wave shape the output from an ASD; and isolated form of the technique used above.

3-Phase Load Reactors
By using a 3-phase load reactor in between the motor and the ASD, one can change the characteristic impedance of the motor or that of the source depending on where the inductor is physically placed. Typical values of impedance used is 0.03 p.u (3 per cent impedance). A higher value of impedance can cause a larger drop across the inductor thereby reducing the fundamental component of the voltage at the motor terminals. This can result in torque reduction and in some cases yield unsatisfactory operation at low speeds and high torque loads. For centrifugal load applications, an inductance of 0.05 p.u. (5 per cent impedance) may also be used without conspicuous deterioration in torque characteristics at practical operating points.

Adding a 3-phase load reactor at the motor end will result in altering the surge impedance of the motor. The line inductance component of the surge impedance of the motor is artificially made high which causes the overall surge impedance of the motor to be higher than normal. The mismatch between the surge impedances of the motor and the cable is aggravated thereby resulting in a higher coefficient of reflection and a higher voltage at the terminating point. Since the terminating point now has the 3-phase inductor first and then the motor terminals, the overvoltage is experienced by the windings of the reactor instead of the motor. The reflected voltage traveling along the conductor back to the sending end will have a higher amplitude because of the larger degree of mismatch at the terminating point.

Adding a 3-phase load reactor at the ASD end will result in altering the surge impedance of the cable. Typically, the surge impedance of the cable is lower than that of the motor. By increasing the surge impedance of the cable artificially, the coefficient of reflection, PR is made lower which reduces the magnitude of reflected wavefront. The reflected voltage travelling back on the conductor towards the motor is reduced which reduces the stress on the cable.

RC Snubbers
The RC snubber is the simplest and lowest cost of all methods employed. In its simplest form it consists of resistors and capacitors configured as shown in Fig. 2. The RC snubber is typically installed at the motor terminals and acts as an impedance matching network. The snubber components are carefully selected to cause the load impedance to match the characteristic impedance of the motor cables. When the motor surge impedance is equal to the line characteristic impedance, then voltage reflection does not occur and excessive voltage will not be experienced at the motor terminals.

Using the same drive/motor combination as above with the motor 1000 feet from the inverter, the performance of the basic snubber network was satisfactory.

The snubber network will also extend the voltage rise time to several microseconds while clamping the peak voltage. The snubber circuit (or impedance matching network) can effectively minimize motor terminal voltage spikes and offer very good protection for the motor. Snubber networks can cost less than $50 but must be located at the motor terminals as they are a cable terminating device. In some cases it may be necessary to match the snubber impedance to the actual line impedance in order to maximize its effect.

LC Filter
The LC filter combines a load reactor and a capacitor network to form a low pass filter as illustrated in Figure 3. The basic concept is that the filter network has a resonant frequency of approximately 1 to 1.5 kHz and frequencies higher than that will be absorbed by the filter and not passed on to the motor. Of course it is important that the inverter switching frequency be set to about 1kHz higher than this resonant frequency to prevent excessive filter current and drive malfunction. In fact, it has been found that the performance of this basic LC filter network, while very good at 2.0 or 2.5 kHz, actually improves as the switching frequency is increased.

The beauty of this filter is that the motor sees a voltage waveform that is nearly sinusoidal. The relative cost of this solution, based on a 5HP drive/motor combination is less than $250.

As the capacitor requirement (for tuning purposes) becomes greater, it is practical to add a dampening resistor in series with the capacitor network. An alternative to this is the LC filter with isolated capacitors.

LC Filter With Isolated Capacitor
This network follows the same basic principles as the basic LC filter except it utilizes an isolation transformer to feed the capacitors. Large values of capacitance can be used because the transformer ratio reduces the capacitor current on the transformer primary side. We get the full effect of the capacitor in conjunction with the series inductor, while minimizing the capacitor current and capacitive reactance as seen by the inverter output circuit. The transformer impedance offers the dampening which is desirable for large values of capacitance. The transformer also offers some inductance which allows the use of a lower inductance value of series reactor thereby reducing the voltage drop and improving motor torque.

The waveforms accomplished with this isolated capacitor technique are quite similar to the waveforms captured with the basic LC filter as the concept is the same. Overall system performance is optimized with this filter network because a sinusoidal waveform is provided for the motor while voltage drop is minimized. Motor life is extended due to the improved waveform. The relative cost of this network, based on 5HP drive/motor combination is about $450.

Mahesh Swamy, and John A. Houdek are with MTE Corporation