
Authors note: specific aspects of safety are addressed herein, however comprehensive procedures are not detailed. It is assumed the operator has sufficient knowledge of electrical theory and safe working practices to use the test instrument in a safe and responsible manner.
Installation
Risk of damage is significant whenever a transformer is moved. This is inherent to the typical
transformer design and modes of transportation employed. Damage can also occur during
unloading and assembly. The damage will often involve a current carrying component such as the
LTC, RA switch or a connector. Damage to such components may result in a change to the DC
resistance measured through them. Hence, it is recommended that the DC resistance be measured
on all on-load and off-load taps prior to energizing.
If the transformer is new the resistance test also serves as a verification of the manufacturers work. Installation measurements should be filed for future reference.
Routine (Scheduled) Transformer Maintenance
Routine maintenance is performed to verify operating integrity and to assure reliability. Tests are
performed to detect incipient problems. What kind of problems will the resistance test detect?
Ratio Adjusting Switch: Contact pressure is usually obtained through the use of springs. In time, metal fatigue will result in lower contact pressure. Oxygen and fault gases (if they exist) will attack the contact surfaces. Additionally, mechanical damage resulting in poor contact pressure is not uncommon. (e.g. A misaligned switch handle linkage may result in switch damage when operated). Such problems will affect the DC resistance measured through the RA switch and may be detected.
Load Tap Changer: The LTC contains the majority of the contacts and connections in the transformer. It is one of few non-static devices in the transformer and is required to transfer load current several thousand times a year. Hence, it demands special consideration during routine maintenance.
In addition to detecting problems associated with high resistance contacts and connectors, the Multi-Amp Transformer Ohmmeter will also detect open circuits as short as 1ms (drop-out test). LTCs transfer load current. They are not designed to interrupt load current. An open circuit would likely result in catastrophic failure. On installation and after maintenance it is certainly prudent to verify operating integrity by checking for open circuits. LTC maintenance often involves considerable disassembly and the test will provide confidence in the reassembly.
It is recommended DC resistance measurements be made on all on-load and off- load taps to detect problems and verify operating integrity of the RA switch and LTC.
Unscheduled Maintenance Troubleshooting
Unscheduled maintenance generally occurs following a system event. The objectives of
unscheduled maintenance are:
Internal Transformer Inspections
Internal inspections are expensive due primarily to the cost of oil processing. When such
opportunities do present themselves the inspection should be planned and thorough. Prior to
dumping the oil, all possible diagnostic tests including the resistance test should be performed.
Safety Considerations: While performing winding resistance tests hazardous voltages could appear on the terminals of the transformer under test and/or the test equipment if appropriate safety precautions are not observed. There are two sources to consider:
It does not matter which terminal is grounded as long there is only one terminal of each winding tied to ground. When test leads are moved to subsequent phases or windings on the transformer it is not necessary to move the ground connections. Ensure the winding is grounded prior to connecting the current and potential test leads, and when disconnecting leads remove the ground last.
D-C Test Current
Should the test circuit become open while DC current is flowing hazardous voltages (possibly
resulting in flash over) will occur. Care must be taken to ensure the test circuit does not
accidentally become open:
Summary of Safety Precautions
Selecting The Proper Current Range
Ensure that the current output selected does not exceed 15% of the rated winding current. This
could cause erroneous readings due to heating of the winding (e.g. A transformer rated 150 kVA,
1 ph: the rated current of the 66 kV winding is 2.25 amps; therefore the test current should not
exceed 340 mA. Select the 50 mA current output.)
Choose the highest current output possible for the expected resistance value without exceeding 15% of rated winding current.
If the instrument will not energize the transformer at the highest current output, check connections and try again. Then, if necessary, reduce the current to the next lower value and repeat.
CAUTION: Do not operate the current selector switch without first discharging the winding (move the current control switch to discharge). Failure to discharge the winding could damage the instrument.
Measurements
Wait until the display has stabilized prior to recording resistance values. Generally, readings
should stabilize in 10-15 seconds. However, the time required for readings to stabilize will vary
based on the rating of the transformer, the winding configuration and the current output selected.
On large transformers with high inductance windings it could take one to two minutes for
readings to stabilize. If the readings don't stabilize within two minutes, check leads, connections
and instrument. It may be necessary to reduce the test current.
Use Form I-89D, Transformer Resistance Test, to record measurements:
Always check the winding schematic on the nameplate, and trace the current path(s) through the windings. The nameplate vector representation may be misleading. Also, check the location of grounds on the windings and ensure the grounds do not shunt the DC test current.
When a winding has both an RA switch (ratio adjusting off-load tap switch) and an LTC (load tapchanger) take measurements as follows:
Prior to taking as left measurements exercise the LTC. Operating the LTC through its full range of taps two to six times should remove the surface oxidation.
When testing windings with LTCs, leave the transformer ohmmeter on while changing from tap to tap. Should the LTC open circuit for even 1 ms, the Transformer Ohmmeter will automatically shut off. Such transformers should not be returned to service as catastrophic failure would be possible.
Part 2 of this article will appear in the April issue. Bruce Hembroff is with Manitoba Hydro.