
A common problem found in Cross-linked Polyethylene (XL-PE) cables is the formation ofelectrochemical or water trees in the insulation. Contaminates, protrusions and irregular surfaces commonly found in extruded cables, coupled with moisture, provide an ideal environment for growth of these trees. It has been found that the AC breakdown strength of treed cables is greatly Laboratory testing of both new and service-aged XLPE cables have revealed two interesting facts:
An alternative to high voltage DC testing of cables has been developed that is non-destructive in nature and not only determines the extent of deterioration but also determines the location of the deterioration.
A van has been manufactured that houses all the necessary equipment to perform the tests. There are two primary diagnostic tests performed they are:
Test Procedure
An initial reflectragram (RG) is made. This is the baseline condition for measurement of anomaliesand also identifies the beginning and the end of the cable as well as location of all splices.
Then 8 kV AC is applied to the cable for a specified period and partial discharges (PD) aremeasured. 12 kV AC is applied for approximately 10 seconds to try to induce partial dischargesand then the voltage is reduced down to 8 kV and PD is measured once again.
The next step involves applying 4 kV AC with a low power-12 kV superimposed pulse on thepositive half cycle of the waveform. Both partial discharge and reflectragrams are made.Finally an 8 kV AC conditioning voltage is applied and final measurements are made.Controlled experiments have shown a high correlation of anomaly detection and location withactual AC breakdown of the insulation. Figure 2 shows a graphic of a section of cable whereanomalies were identified and corresponding failures.
The key here is that where anomalies were identified, there were failures. Where no anomalieswere not found, there were no failures.
Since May of 1994, 310 cables have been tested. The table below shows a breakdown of type ofcable tested:
| Type of Cable | Quantity |
|---|---|
| PILC | 30 |
| XLPE | 265 |
| PILC/XLPE | 6 |
| EPR/XLPE | 9 |
Typical Results Of Cable Testing Measurement And Location of Anomalies and PD Sites Conclusions Phase A: Conclusions Phase B: Conclusions Phase C: A summary of results to date show some enlightening facts. Summary Several utilities have benefited from this type of cable testing. Not only are they able to determinethe extent and location of defects and assist in reducing unplanned outages to key customers, theynow have a basis to proactively plan a cable replacement program. In the past decisions weremade based on age, past failures and other subjective data. Today, these decisions can be made using a non-destructive testing method with objective data.By prioritizing cable replacement decisions one can defer certain cable replacement costs whichcan add up to millions of dollars and help ensure reliable service to their customers. Claude Kane is with Westinghouse Electric Corporation, located in Minnetonka, MN.
Legend for charts (left):
PD [pCl] - Level of partial discharge in pico-coulombs
an [%] - Anomaly location and the percent change in surge impedance
=END - End of cable
Feeder: PMH11-264 to Disconnect # 1212
Cable Length: 647 m (2,122 ft.)
Cable Type: XLPE/500/AL
Small surge impedance anomalies at 1,263 feet. Splice at 1,095 feet has a very high level of partialdischarge. Recommend replacement of splice.
Surge impedance anomalies were not observed. Partial discharges were noted at 24 feet. Werecommend this section of cable be replaced.
Several small surge impedance anomalies were observed. Partial discharges were also observed.Recommend replacement of cable PMH11-264 to splice at 1,095 feet.
It has been found the testing XLPE cables with high voltage DC does not necessarily prove thereliability of the cable. Often, improper DC testing can cause in-service failure of a cable. A newnon-destructive testing service has been introduced by DIACS International and WestinghouseElectric Corporation that can identify the magnitude and location of active insulation degradationand large water trees.